Flow Loss Nomograph
Williams-Hazen formula · C = 150 (thermoplastic pipe)
GPM
PSI/100ft:
13.252
·
Velocity:
7.98
ft/sec
⚠ high velocity
DR-9 · 250 PSI · 3/4" · 13 GPM
DR-9 · 250 PSI · 3/4" · I.D. 0.816" · 13 GPM · 13.252 PSI/100ft · 7.98 ft/sec ⚠ high velocity
Values are calculated using the Williams-Hazen formula (C = 150) and are provided for reference only. Interstate Plastic, Inc. makes no warranty as to accuracy or fitness for any particular use. Consult a licensed engineer for system design.