Friction Loss Calculator
Williams-Hazen formula · C = 150 (thermoplastic pipe)
GPM
PSI Loss per 100 ft
4.411
Velocity (ft/sec)
5.07
⚠ Velocities over 5 ft/sec should be selected with caution.
DR-9 · 250 PSI · 1" · 13 GPM
DR-9 · 250 PSI · 1" · I.D. 1.023" · 13 GPM · 4.411 PSI Loss per 100 ft · 5.07 ft/sec ⚠ high velocity
Values are calculated using the Williams-Hazen formula (C = 150) and are provided for reference only. Interstate Plastic, Inc. makes no warranty as to accuracy or fitness for any particular use. Consult a licensed engineer for system design.