Flow Loss Nomograph
Williams-Hazen formula · C = 150 (thermoplastic pipe)
GPM
PSI/100ft:
3.194
·
Velocity:
4.87
ft/sec
SDR-9 · 250 PSI · 1-1/2" · 19 GPM
SDR-9 · 250 PSI · 1-1/2" · I.D. 1.263" · 19 GPM · 3.194 PSI/100ft · 4.87 ft/sec
Values are calculated using the Williams-Hazen formula (C = 150) and are provided for reference only. Interstate Plastic, Inc. makes no warranty as to accuracy or fitness for any particular use. Consult a licensed engineer for system design.