Flow Loss Nomograph
Williams-Hazen formula · C = 150 (thermoplastic pipe)
GPM
PSI/100ft:
4.725
·
Velocity:
7.02
ft/sec
⚠ high velocity
DR-13.5 · 160 PSI · 1-1/2" · 45 GPM
DR-13.5 · 160 PSI · 1-1/2" · I.D. 1.618" · 45 GPM · 4.725 PSI/100ft · 7.02 ft/sec ⚠ high velocity
Values are calculated using the Williams-Hazen formula (C = 150) and are provided for reference only. Interstate Plastic, Inc. makes no warranty as to accuracy or fitness for any particular use. Consult a licensed engineer for system design.