Flow Loss Nomograph
Williams-Hazen formula · C = 150 (thermoplastic pipe)
GPM
PSI/100ft:
7.254
·
Velocity:
8.97
ft/sec
⚠ high velocity
SDR-9 · 250 PSI · 2" · 60 GPM
SDR-9 · 250 PSI · 2" · I.D. 1.653" · 60 GPM · 7.254 PSI/100ft · 8.97 ft/sec ⚠ high velocity
Values are calculated using the Williams-Hazen formula (C = 150) and are provided for reference only. Interstate Plastic, Inc. makes no warranty as to accuracy or fitness for any particular use. Consult a licensed engineer for system design.