Flow Loss Nomograph
Williams-Hazen formula · C = 150 (thermoplastic pipe)
GPM
PSI/100ft:
10.153
·
Velocity:
6.17
ft/sec
⚠ high velocity
SDR-9 · 250 PSI · 3/4" · 7 GPM
SDR-9 · 250 PSI · 3/4" · I.D. 0.681" · 7 GPM · 10.153 PSI/100ft · 6.17 ft/sec ⚠ high velocity
Values are calculated using the Williams-Hazen formula (C = 150) and are provided for reference only. Interstate Plastic, Inc. makes no warranty as to accuracy or fitness for any particular use. Consult a licensed engineer for system design.