Friction Loss Calculator
Williams-Hazen formula · C = 150 (thermoplastic pipe)
GPM
PSI Loss per 100 ft
5.624
Velocity (ft/sec)
8.38
⚠ Velocities over 5 ft/sec should be selected with caution.
DR-9 · 250 PSI · 2" · 70 GPM
DR-9 · 250 PSI · 2" · I.D. 1.847" · 70 GPM · 5.624 PSI Loss per 100 ft · 8.38 ft/sec ⚠ high velocity
Values are calculated using the Williams-Hazen formula (C = 150) and are provided for reference only. Interstate Plastic, Inc. makes no warranty as to accuracy or fitness for any particular use. Consult a licensed engineer for system design.